4 General settings
4.1 Time and date
4.1.1 Mode of operation
The RMS705B has a yearly clock with time, weekday and date.
Y
early clock
Two selectable time
formats
The followi
ng time formats are available:
24 h:
The date is displayed as dd.mm.yyyy (day.month.year).
Example: 01.01.2010
The time is displayed as hh:mm (hours:minutes).
Example: 15:56
am/pm:
The date is displayed as mm/dd/yy (month/day/year).
Example: 05/31/06
The time is displayed as hh:mm am/pm (hours:minutes am/pm).
Example: 03:56 PM
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Device >
Setting values
Operating line Range Factory setting
Time format 24 hours,
12 hours (am/pm)
24 h
Main menu > Time of day/date >
Operating line Range Factory setting
Time of day 00:00...24:00 00:00
Date 01.01...31.12 01.01
Year 2000...2080 Current
Changeover from daylight saving to standard time and vice-versa is automatic as
per the set values.
Da
ylight
saving/standard time
changeover
The date
s of the earliest changeover can be adjusted in case of corresponding
standard changes.
Main menu > Time of day/date >
Setting values
Operating line Range Factory setting
Summer time start 01.01. … 31.12 25.03
Winter time start 01.01. … 31.12 25.10
Notes The dates set for changeover from standard to daylight saving time, or vice
versa, ensure that on the first Sunday after that date the time changes from
02:00 (standard time) to 03:00 (daylight saving time), and from 03:00 (daylight
saving time) to 02:00 (standard time).
If both dates are set to the same date, daylight saving/standard time changeover
does not work.
23 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies General settings 01.04.2010