5.2 Analog inputs
See Section 5.1.1 for activating analog inputs.
You can enter the following settings for analog inputs: Type, Measured range,
Correction.
5.2.1 Type
You can select "Type" if the unit is °C (identifier °C and outside temperature). The
following types are available:
Ni1000*
2xNi1000*
T1
Pt1000
DC 0...10 V
* Physically, the sensing element types LG-Ni1000, 2x LG-Ni1000 must be used (see Section 5.2.2).
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Setting values
Operating line Range Factory setting
Type Ni1000, 2xNi1000, T1,
Pt1000, 0…10 V
Ni1000
Note
s
If the unit is not °C, the "Type" is always DC 0...10 V.
Physically, the sensing element types LG-Ni1000, 2x LG-Ni1000 must be used
(see Section 5.2.2).