User Manual

5.2.5 Connection examples for sensors
Temperature measurement with passive temperature sensor using LG-Ni 1000
sensing element.
Example 1
Main menu > Commissioning > Extra configuration > Input identifier >
Input config
uration
Operating lin
e Setting
N.X1 °C
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Setting values
Operating line Setting
Type Ni1000
G
G
G0
X...
M
G0
B...
N
3123A06
AC 24 V
BM
LG-Ni 1000
Con
nection diagram
B… Passive sensor
Average temperature measurement with 2 passive sensors using LG-Ni1000
sensing elements.
Example 2
Main menu > Commissioning > Extra configuration > Input identifier >
Input config
uration
Operating lin
e Setting
N.X1 °C
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Setting values
Operating line Setting
Type 2xNi1000
G
G
G0
X...
M
G0
B...
N
3123A07
AC 24 V
BM
LG-Ni 1000
BM
LG-Ni 1000
B...
Con
nection diagram
B… Passive sensor
33 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Inputs 01.04.2010