5.6 Outside temperature
5.6.1 Possible connections
The outside temperature can be provided by different sources:
Outside temperature connected locally to terminal.
Outside temperature via bus.
The following variants are available:
Variant Effect Diagram
Outside temperature at
terminal.
Communication outside
temperature not active.
RMS705B operates with own
outside temperature.
No effect on bus.
T
Outside temperature at
terminal.
Communication outside
temperature active.
RMS705B operates with own
outside temperature.
Using the bus, the outside
temperature is also provided to
other controllers.
T
No outside temperature at
terminal.
Communication outside
temperature active.
RMS705B operates with outside
temperature provided by another
controller on the bus.
3123Z06
T
No outside temperature at
terminal.
Communication outside
temperature not active.
RMS705B has no outside
temperature.
T
5.6.2 Outside temperature at terminal
See Section 5.2 "Analog inputs" for settings and the connection diagram for the
outside temperature at the terminal.
Main menu > Commissioning > Extra configuration > Input identifier >
Configuration
Operating line Adjustable values / Comment
…X… Activate the function by assigning the "Outside temperature"
value to the input.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Setting values
Operating line Range Factory setting
Type Ni1000, 2xNi1000, T1, Pt1000,
0…10 V
Ni1000
Value low Depending on selected type Type-dependent
Value high Depending on selected type Type-dependent
Correction
3.0… 3.0 K
0 K
40 / 216