5.6.5 Troubleshooting
When you exit the "Commissioning" menu, a check is carried out to see if the
outside temperature is connected. Message "[...X...] sensor error" is displayed if
the outside temperature is connected at this point and missing later.
For each system, only one outside temperature can be sent within the same zone
(only one outside temperature master).
Message ">1 outside temperature sensor" is displayed if several controllers send
outside temperatures within the same zone. The fault is sent by the controllers
sending and receiving outside temperature signals to and from the same zone.
Message "Outside temp sensor error" is displayed if the controller expects an
outside temperature signal via the bus and the signal is not sent.
No. Text Effect
101…
264
[N.X1] sensor error…
RMZ788(2).X4 sensor error
Non-urgent message; must not be
acknowledged.
11 >1 outside temperature
sensor
Urgent message; must be
acknowledged.
10 Outside temp sensor error Non-urgent message; must not be
acknowledged.
Fault messa
ges
If other outside temperature signals are available on the bus, any of them are used
randomly.
5.7 Assign texts
For every input, the texts can be adjusted via operation.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Inputs > ...X...
Setting values
Operating line Range Factory setting
N.Xx Max. 20 characters N.Xx
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on h
ow to reset them.