6.2.4 Fault messages
The following fault messages are generated during violation (above and below) if
the corresponding times for "Event duration min/max" or "Event cycle min/max" are
greater than 0.
You must acknowledge these fault messages.
No. Text Effect
9111 [Logger 1] on before cycle min Fault priority as set;
must be acknowledged and reset.
9112 [Logger 1] on after cycle max Fault priority as set;
must be acknowledged and reset.
9113 [Logger 1] off before dur min Fault priority as set;
must be acknowledged and reset.
9114 [Logger 1] off after dur max Fault priority as set;
must be acknowledged and reset.
9121 [Logger 2] on before cycle min Fault priority as set;
must be acknowledged and reset.
9122 [Logger 2] on after cycle max Fault priority as set;
must be acknowledged and reset.
9123 [Logger 2] off before dur min Fault priority as set;
must be acknowledged and reset.
9124 [Logger 2] off after dur max Fault priority as set;
must be acknowledged and reset.
9131 [Logger 3] on before cycle min Fault priority as set;
must be acknowledged and reset.
9132 [Logger 3] on after cycle max Fault priority as set;
must be acknowledged and reset.
9133 [Logger 3] off before dur min Fault priority as set;
must be acknowledged and reset.
9134 [Logger 3] off after dur max Fault priority as set;
must be acknowledged and reset.
9141 [Logger 4] on before cycle min Fault priority as set;
must be acknowledged and reset.
9142 [Logger 4] on after cycle max Fault priority as set;
must be acknowledged and reset.
9143 [Logger 4] off before dur min Fault priority as set;
must be acknowledged and reset.
9144 [Logger 4] off after dur max Fault priority as set;
must be acknowledged and reset.
Fault messa
ges
6.2.5 Troubleshooting
Changing the current data or time during event logging may result in premature
triggering of a fault message.
Notes
After changing the extra configuration in the event logger, previous logs are
deleted when the extra configuration is closed.
No event logging takes place if "Limit value on" = "Limit value off".
48 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Data acquisition 01.04.2010