User Manual
6.3.4 Maintenance message
A maintenance message can be assigned to each operating hours counter,
e.g.: "Service Fan SA".
Both "Text for: Service required" and "Service interval" are freely selectable.
"Service interval" specifies the number of operating hours until the next service. No
maintenance message is sent if "Service interval" is set to 0 h.
The fault priority is set to "Not urgent".
Main menu > Commissioning > Settings > … or
Select interva
l and enter
text for maintenance
Main menu > Settings > Data acquisition > Operating hours > Operating hours 1…4 >
Operating line Range Factory setting
Service interval 0…99999 h 0 h
Text for: Service required Max. 20 characters [O'hrs 1] serv req
A corresponding maintenance message is generated once the counter "Operating
hours since service" reaches the value for the maintenance interval.
No. Text Effect
1911 [O'hrs 1] serv req Non-urgent fault.
1912 [O'hrs 2] serv req
Non-urgent fault.
1913 [O'hrs 3] serv req
Non-urgent fault.
1914 [O'hrs 4] serv req
Non-urgent fault.
Maintena
nce messages
6.3.5 Operating hours display
Main menu > Data acquisition > Operating hours 1…4 >
D
isplay values
Operating lin
e Range Factory setting
Operating hours x* Display 0…99,999 h
Operating hours since service Display 0…99,999 h
Reset** No, Yes No
* Display of the operating hours run to date. The counter counts to max. 99,999 hours and then rolls
over to 0.
** This setting resets "Operating hours since service" to 0 hours and deletes the maintenance message.
51 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Data acquisition 01.04.2010