User Manual

6.5.2 Limits for output and user-defined unit
The calculated output signal of the modulating output (Y) can be limited high and
low.
In addition, you can assign a user-defined unit.
The output result's unit (K, kW, etc.) is entered as characters and displayed
together with the output value.
Main menu > Commissioning > Settings > … or
Setting
Main menu > Settings > Data acquisition > Calculator > Calculator 1…2 >
Operating line Range Factory setting
Unit Max. 20 characters
Value low -50…9999 0
Value high -50…9999 100
Value low and Value high only limit the DC 0…10 V signal run to the Y-output.
10 V
0 %
0 V
3124D013124D01en
Value low Value high
6.5.3 Assign texts
A specific text can be assigned to each calculator.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Data acquisition > Calculator > Calculator 1…2 >
Free text
Operating line Range Factory setting
Calculator 1…2 Max. 20 characters Calculator 1…2
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on h
ow to reset them.
58 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Data acquisition 01.04.2010