User Manual

The settings have the following effect:
Entry Effect Diagram
Autonomous The time switch only acts locally on the
RMS705B.
Slave The time switch in RMS705B is not active.
The acting time switch is that one acting on
the geographical zone set on this controller
as the time switch receiving zone (time
switch slave (apartment)). The external time
switch must be set as the time switch
master.
3123Z08
Enter the "Geographical zone (apartment)" of the controller that is to receive the
time switch data during time switch operation "Slave".
If the time switch is operated as a "Slave", the output of the relevant time switch
assumes the following states:
Operating mode "Master time
switch" (RMx)
State of time switch output (RMS705B)
Comfort On
Precomfort Set in operating line "Transformation
Precomfort": On or Off
Economy Off
S
tate of time switch
output for slave operation
Main menu > Commissioning > Communication > Time switch > Time switch 1…6 >
Setting values
Operating line Range Factory setting
Time switch slave (apartment) ---, 1..126 ---
Time switch operation* Autonomous, Slave
Transformation Precomfort Off, On On
* Information line: Result of the setting.
7.1.2 Entries
You can select a specific 24-hour profile for the following days.
Main menu > Time switch 1…6 >
Set time s
witch
Operating lin
e Range Factory setting
Monday to Sunday On, Off 06:00
22:00
Special day On, Off 06:00
22:00
You can enter for each day max. 6 entries in the 24-hour program.
Each entry must have the time of day and the required operating mode (On/Off).
You can copy data entered for a day to other days. If, for example, you entered
data for Monday, you can copy the same profile to all other working days (Monday
through Friday).
Copy 24-hour profiles
61 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies 7-day time switch 01.04.2010