7.2.4 Calendar entry
Max 16 entries are possible. The entries are sorted in chronological order. The
following is required for each entry:
Date, year and start time.
Date and end time.
Reason for entry (holidays or special day).
Main menu > Holidays/special days >
Setting values
Operating line Range Factory setting
Entry 1...16 Start, End, Reason
You can enter annually recurring holidays or special days by entering an asterisk
"*" for the annual setting. Otherwise, the entries made are automatically deleted at
the end of the holidays or special days.
Note
The following applies to two overlapping entries: Special days take priority over
holidays. As a result, you can predefine a special day during vacation/holidays.
Priority
Theater play in schoolhouse during vacation/holidays.
Example for speci
al day
during holidays/vacation
Note
At the end of the holiday
s or special day, operation according to the normal 7-day
program is resumed. In this transition, you may not be able to start optimum start
control (e.g. boost heating) in time. We thus recommend to move down the end of
the holidays/vacation allowing the plant sufficient time to adapt to the respective
setpoints.
7.2.5 Control input "Holidays/special days"
You can also activate holidays and special days via digital inputs. To do this, assign
digital inputs.
Main menu > Commissioning > Extra configuration > Holidays/special days >
Config
uration
Operating lin
e Adjustable values / Comment
Holiday input ---, N.X1, N.X2,...
Special day input ---, N.X1, N.X2,...
These inputs work only if Holidays/special day operation is set as "Autonomous"
or "Master".
Notes
Activation of special days or holidays via digital inputs is not entered in the
holidays/special day program, eliminating recurrence.