User Manual
8.1.1 Activate the logic
Activate the logic by configuring at least 1 input or the operation selector.
Use menu "Extra configuration" to configure logic functions for Logic A, B, and C.
The "Operation selector" setting in the operating line selects if the operation
selector is to be displayed in the main menu at the user level.
The operation selector allows users manual manipulations. No warning is
displayed during manual manipulations.
Note
Main menu > Commissioning > Extra configuration > Aggregates > Logic functions > Logic
1...10 >
Config
uration
Operating lin
e Adjustable values Factory setting
[Logic A] input 1 ---, X1, X2, ... ---
[Logic A] input 2 ---, X1, X2, ... ---
[Logic A] input 3 ---, X1, X2, ... ---
[Logic B] input 1 ---, X1, X2, ... ---
[Logic B] input 2 ---, X1, X2, ... ---
[Logic A] function AND, NAND, OR, NOR OR
[Logic B] function AND, NAND, OR, NOR NOR
[Logic C] function AND, NAND, OR, NOR, EXOR, EXNOR AND
Logic relay ---, N.Q1, N.Q2, .../ (free outputs only) ---
Operation selector Yes, No No
Time format h:m, m:s m:s
You can select format "Hours:Minutes" as an extended time format (> 59.59 m.s)
for the logic function.
Important: The changeover impacts all time-related parameters of the logic
function block (switch-on/off delay and min. switch-on/off time).
Note
s
Time format "h:m" offers a 10-minute increment setting range.
8.1.2 Assign texts
You can assign a specific text to each logic and operation selector. The text is
displayed on the menu and in the operating line.
Main menu > Commissioning > Settings > .... or
Setting values
Main menu > Settings > Aggregates > Logic functions > Logic 1...10 >
Operating line Range Factory setting
Logic 1...10 Max. 20 characters Logic 1...10
Operation selector 1...10 Max. 20 characters Operation selector 1...10
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on h
ow to reset them.