User Manual

8.1.3 Setting values switching value On and Off
The logic can process digital and analog signals. Setting values "[Logic x switching
value n] on" and "[Logic x switching value n] off" are used to convert a continuous
signal to a 2-position signal (On/Off).
Main menu > Commissioning > Settings > .... or
Setting values
Main menu > Settings > Aggregates > Logic functions Logic 1...10 >
Operating line Range Factory setting
[Logic A switching value 1] on Depending on selected type Type-dependent
[Logic A switching value 1] off Depending on selected type Type-dependent
[Logic A switching value 2] on Depending on selected type Type-dependent
[Logic A switching value 2] off Depending on selected type Type-dependent
[Logic A switching value 3] on Depending on selected type Type-dependent
[Logic A switching value 3] off Depending on selected type Type-dependent
[Logic B switching value 1] on Depending on selected type Type-dependent
[Logic B switching value 1] off Depending on selected type Type-dependent
[Logic B switching value 2] on Depending on selected type Type-dependent
[Logic B switching value 2] off Depending on selected type Type-dependent
8.1.4 Switch-on/switch-off delay
For the logic output, a switch-on and switch-off delay can be set.
Main menu > Commissioning > Settings > .... or
Setting values
Main menu > Settings > Aggregates > Logic functions Logic 1...10 >
Operating line Range Factory setting
Switch-on delay 00.00...59.59 m.s or*
00.00...23.50 h.m
00.00 m.s
Switch-off delay 00.00...59.59 m.s or*
00.00...23.50 h.m
00.00 m.s
* See Notes on the time format in Section 8.1.1
The switch-on delay always acts on the switch-on command; the switch-off delay
on the switch-off command.
Note
8.1.5 Minimum on time
For the logic output, a min. switch-on time can be set. Thus, the output remains set
to On for the set time when a switch-on command is received.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions Logic 1...10 >
Setting values
Operating line Range Factory setting
On time minimum 00.00...59.59 m.s or*
00.00...23.50 h.m
00.00 m.s
* See Notes on the time format in Section 8.1.1
The minimum on-time always takes effect after a switch-on command.
70 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Aggregates 01.04.2010