User Manual

8.2.2 Assign texts
You can assign a text to each comparator. The text is displayed on the menu and in
the operating line.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions > Comparator 1...2 >
Operating line Range Factory setting
Comparator 1…2 Max. 20 characters Comparator 1…2
Setting values
See Section 16.4 "Editable texts RMS705B" for an overview of all editable texts
and on h
ow to reset them.
8.2.3 Upper and lower limit value
The comparator switches on when Limit value on is exceeded, and off when the
value is below Limit value off.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions > Comparator 1...2 >
Setting values
Operating line Range Factory setting
Limit value on Depending on selected type. Type-dependent.
Limit value off Depending on selected type. Type-dependent.
8.2.4 Switch-on/switch-off delay
You can set a switch-on and switch-off delay for the comparator output.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions > Comparator 1...2 >
Setting values
Operating line Range Factory setting
Switch-on delay 00.00...59.59 m.s or*
00.00...23.50 h.m
00.00 m.s
Switch-off delay 00.00...59.59 m.s or*
00.00...23.50 h.m
00.00 m.s
* See Notes on the time format in Section 8.2.1
The "Switch-on delay" acts on the switch-on command, the "Switch-off delay" on
the switch-off command.
75 / 216
Siemens Switching and monitoring device RMS705B CE1P3124en
Building Technologies Aggregates 01.04.2010