8.2.5 Minimum on time
For the comparator output, a minimum on-time can be set, i.e., when a switch-on
command is issued, the output remains active at least for the set min. switch-on
time.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions > Comparator 1...2 >
Setting values
Operating line Range Factory setting
On time minimum 00.00...59.59 m.s or*
00.00...23.50 h.m
00.00 m.s
* See Notes on the time format in Section 8.2.1
The "On time minimum" always takes effect after a switch-on command.
8.2.6 Minimum off time
The minimum off time prevents aggregates from cycling too frequently.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions > Comparator 1...2 >
Setting values
Operating line Range Factory setting
Off time minimum 00.00...59.59 m.s or*
00.00...23.50 h.m
00.00 m.s
* See Notes on the time format in Section 8.2.1
The "Off time minimum" always takes effect after a switch-off command.
8.2.7 Display values
Operation displays the output state of the comparator.
Main menu > Aggregates > Comparator 1...2 >
D
isplay values
Operating lin
e Comment
State Display of present state: Off, On.
Switching value A
Switching value B
8.2.8 Wiring test
You can directly switch on and off the comparator's relays during the wiring test.
Main menu > Commissioning > Wiring test > Outputs >
Wirin
g test
Operating lin
e Comment
Comparator 1 Off, On
Comparator 2 Off, On