Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Optimum start control (basic type A) 03.10.2011
Main menu > Plant operation >
Operating line Comments
Cause Displays present plant operating mode [Optimum start
control]
Optimum start control is only enabled together with the time switch.
The adapted optimum start control can result in confusing results, if the functions
such as supply air / sequence limitations, sequence locks by outside temperature,
controller timeout, etc. influence control. In applications, we recommend the setting
"On: Values fix".
22.2.1 Priorities
The following priorities apply to activating optimum start control:
1. On / Off during wiring test.
2. Smoke extraction.
3. Fire alarm off.
4. Frost.
5. Room/plant operating mode specifications.
6. Optimum start control.
7. Sustained mode.
8. Night cooling.