User Manual

248/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Faults 03.10.2011
The text for the universal fault inputs can be adjusted via the operator unit.
Displayed locally in the event of a fault and transmitted via the bus.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Faults > Fault input 1…10 >
Operating line Range Factory setting
Fault text x
Max. 20 characters
[Fault input x] Fault
No. Standard text Effect
9000
>1 fault input faulty
Urgent message; does not require
acknowledgement
(Effect can be set for each fault input)
9001
[Fault input 1] fault
As per the settings
9002
[Fault input 2] fault
ditto
9003
[Fault input 3] fault ditto
9004
[Fault input 4] fault ditto
9005
[Fault input 5] fault ditto
9006
[Fault input 6] fault ditto
9007
[Fault input 7] fault ditto
9008
[Fault input 8] fault ditto
9009
[Fault input 9] fault ditto
9010
[Fault input 10] fault ditto
The fault with the highest priority is sent over the KNX bus. If more than one fault
with priority "urgent" is pending at the fault input, “>1 fault input faulty” is sent with
the highest priority. Without this fault message, only the message from one fault
input would be known. The newly arriving fault message can be displayed on the
Info level under "Fault status message bus".
24.4 Predefined fault inputs
Predefined fault inputs are available depending on the controller basic type:
Filter supervision
Fire alarm off
Smoke extraction supply air
Some extraction extract air
24.4.1 Filter supervision (basic types A and P)
An input must be assigned to this function to activate it (basic types A and P).
Main menu > Commissioning > Extra configuration > Faults >
Operating line Adjustable values / remarks
Filter supervision ---, N.X1, N.X2, ...
The following settings available for filter supervision:
Fault status signal delay.
Elapsed time until a pending fault generates a fault message
Limit value "Fault on": Limit value from which the fault status message is
generated
Limit value "Fault off": Limit value for the normal state
Fault texts
Fault status messages
>1 fault input faulty
Configuration