User Manual
58/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Operating modes 03.10.2011
QAW740 RM.. RM..
3150Z03
en
Geogr zone = 5
Room unit
Room operating mode Room operating mode
Geogr zone = 5 Geogr zone = 5
Ventilation 1 Ventilation 2
Room control comb. =
Master
Room control comb. =
Slave external setpoints
The slave ventilation controllers apply the same operating mode as the master
within the combination. With regard to setpoints, individual setpoints or the
master's setpoints can be applied.
Case
Room control
combination
Effect
Common room operating
mode, common setpoints
Slave external setpoint The heating/cooling setpoints for Comfort,
Precomfort and Economy of the master
are assumed by the slave ventilation controller
and its setpoints overwritten.
The setpoints can no longer be set at the slave
ventilation controllers. If readjustment is
needed, it must be entered on the ventilation
controller (master).
Common room operating
mode, individual setpoints
Slave internal setpoint The slave ventilation controller uses its own
internal heating/cooling setpoints.
Setting for slave
ventilation controller