Assortment / System Description

10
Immersion temperature controllers
Differential temperature controllers RLE127 and RLE127.QAZ
RLE127 differential temperature controller with immersion sensor (immersion
length 150 mm). RLE127.QAZ complete with collector sensor QAP21.1.
Calculation of the temperature differential also requires an LG-Ni1000 temperature
sensor. 2 relay outputs to control thermal actuators or circulating and charging
pumps (for switching AC 24…230 V, max. 2 A).
Control of temperature differential between heat source and heat consumer
Demand-dependent changeover to a second heat source
Maintenance of a minimum charging temperature
Consideration can be given to an absolute temperature
Frost protection, remote setpoint adjustment
Solar plants with storage tanks
Swimming pool heating with solar collectors
Heat storage plants with 2 storage tanks
Heat generation plants with 1 boiler
Solar plant with heat exchanger and storage tank
Differential temperature control of collector and storage tank. Temperature sensor
B3 acquires the temperature in the heat exchanger. The storage tank is charged
only when the heat exchanger temperature at B3 reaches the setpoint (controller
N1).
N1
E1
B2
E2
M1
T
B3
M2
3337S04
T
B2
B3
E1
E2
M1
M2
N1
Collector sensor QAP21.2
Heat exchanger sensor
Storage tank
Collector
Charging pump 1 (solar circuit)
Charging pump 2 (storage tank
circuit)
Differential temperature controller
RLE127.QAZ
Immersion temperature controller RLE132
Immersion temperature controller (immersion length 150 mm). Modulating control
via actuating device on the water side (seat or slipper valve). Positioning signal
(3-pos.) acting on electromotoric actuator (for switching AC 24…230 V, max. 2 A).
Used as a controller or minimum/maximum limiter
Control in Economy mode (setpoint lowered)
Control in Boost mode (setpoint raised)
Minimum or maximum limitation of flow or return temperature
Setpoint changeover via external contact
Load-dependent switching contact (e.g. pump release)
Outside temperature compensation, remote setpoint adjustment
Frost protection
Use
Application example