Assortment / System Description

21
Applications programmed in controller RLU236 (for all, see Data Sheet N3101).
Application Application no./description Plant diagram
A01 ADA007 LU3 HQ
Extract air (room) temperature control with electric air heater.
Options:
- Minimum and maximum limitation of supply air temperature
- Outside temperature-dependent functions
- 6-stage electric air heater
- Comfort/Economy changeover; remote setpoint adjuster (relative)
- Comfort/Protection changeover (time switch)
S01
T
N.X3
B9
E1
N.Q1
N.Q2
N.Q3
N.Q4
N.Q5
N.Q6
N.Y1
N.X2
B1
T
N.X1
B2
T
N.X4
R5
T
N.D1
S5
N.D2
S6
A04 ADB008 LU3 HQ
Supply air temperature control with dx cooler.
Options:
- Room temperature cascade control
- Outside temperature-dependent functions
- 6-stage dx cooler
- Comfort/Economy changeover; remote setpoint adjuster (relative)
- Comfort/Protection changeover (time switch)
S5
S6
M7
N.Q1
N.Q2
N.Q3
N.Q4
N.Q5
N.Q6
Y7
U04 ADI004 LU3 HQ
Extract air (room) humidity control (r.h.) with dx cooler.
Options:
- Additional maximum selection from internal and external signal
- Room temperature-dependent shifting of humidity setpoint
- 6-stage dx cooler
- Comfort/Economy changeover; remote setpoint adjuster
(absolute)
- Comfort/Protection changeover (time switch)
S01
N.X2
M7
N.Q1
N.Q2
N.Q3
N.Q4
N.Q5
N.Q6
N.X1
[%]
B12
ϕ
N.X3
B5
T
N.X4
R5
T
N.D1
S5
N.D2
S6
N.Y1
Y7
Application A10 (APPL ID) according to AEFL01 LU3 HQ in HIT.
Examples with RLU236
In HIT