Assortment / System Description

23
When activating an application (e.g. M01 on menu APPL ID), the respective inputs
and outputs, functions and parameters are automatically activated; parameters not
required will be deactivated.
Every programmed application can be modified. On the APPL ID menu, ADAP
indicates that the programmed application was changed (adapted) or – if that is
not the case – ORIG is displayed, meaning "original".
Application examples Mxx: Measuring variables as input signals
Application Description Connection diagram
M01
Selection of minimum and maximum input signal from all
pending passive input signals.
A01
BM
DC 0...10 V
MIN
5 x LG-Ni 1000
G
G0
X1 M
X2 M G1 X3 M X4 M G1 X5 M
Y2 G0G1Y1 G0G1
DC 0...10 V
MAX
BM BM BM BM
M05
Calculation of average of 2 active and 3 passive input
signals.
A01
BM
3 x LG-Ni 1000
X3 M X4 M G1 X5 M
Y2 G0G1
DC 0...10 V
AVR
DC 0...10 V
AVR
G
G0
X1 M X2 M G1
Y1 G0G1
BMBM
G G
2 x DC 0...10 V
BM
BM
Application examples Exx: Enthalpy calculations
Application Description Connection diagram
E01
Calculation of enthalpies of 1 passive temperature signal
and 1 active humidity signal.
DC 0...10 V
ENTH 1
[kJ/kg]
DC 0...10 V
ENTH 2
[kJ/kg]
A01
LG-Ni 1000
X3 M X4 M G1 X5 M
Y2 G0G1
G
G0
X1 M X2 M G1
Y1 G0G1
BM
G
DC 0...10 V
BM
G
BM
DC 0...10 V
LG-Ni 1000
BM
E03
Calculation of absolute humidity and enthalpy of 1 passive
temperature signal and 1 active humidity signal.
DC 0...10 V
ABSHU 1
[g/kg]
DC 0...10 V
ENTH 1
[kJ/kg]
A01
X3 M X4 M G1 X5 M
Y2 G0G1
G
G0
X1 M X2 M G1
Y1 G0G1
G
DC 0...10 V
BM
LG-Ni 1000
BM
Application example D01: Signal processing
Application Description Connection diagram
D01
Doubling of signal for sequential control of
pumps, valves and fans.
Legend
N1 = Controller (or active device)
U2 = SEZ220 signal converter
N1 U2
Y2
X1
10 V5 V
0 V
Y1
X1
5 V0 V
10 V
G
G0 Y1
DC 0 ... 10 V
A01
G
G0
X1 M X2 M
G1
X3 M X4 M G1 X5
M
Y2 G0G1Y1 G0G1
Programmed
applications
Modifying