Assortment / System Description

26
Controls RM..
Synco 700 controls RM.. contain programmed applications that can be straight-
forwardly activated. For the free configuration of new customized applications,
basic types in accordance with the basic device functions are available. The
devices can be easily and efficiently installed and commissioned.
The controls consist of terminal base and electronics section which plugs into the
terminal base. Integrated in the terminal base is the connection facility (electrical
and mechanical) for the extension module.
3144Z01
1
23
45 67 8 5 10
9
11
11
1
2
3
4
5
6
7
8
9
10
11
Connection facility for service tool OCI700.1
Connection facility for operator unit RMZ790
LED "Run" (green) for indication of
operating state (power on, no fault)
Button "
" with LED (red) for fault indication
and acknowledgement
Opening for plug-in type operator unit
RMZ790
Button "Prog" for changing between normal
and addressing mode
LED "Prog" to indicate addressing mode
(adoption of physical KNX device address)
Catch for fitting the device to a rail
Fixing facility for cable tie
Connection facility for extension module
Rest for terminal cover
Mounting and installation
The controls and extension modules are designed for …
mounting in a control panel (front or rear),
fitting to a standard mounting rail as per EN 60715-TH 35-7.5,
wall mounting with 2 fixing screws.
Controls with an attached RMZ790 operator unit can be mounted in a control panel
such that when the control panel door is closed, the unit protrudes through the
cutout, giving the plant operator access to the display and the operating elements.
RMZ780
3110Z25
Note: In place of the attachable RMZ790 operator unit it is also possible to use the handheld operator
unit RMZ791.
Brief description
Basic design
Mounting
Control panel