Assortment / System Description

32
Every sequence with modulating control (modulating output, step switch, mixed
air damper, heat recovery system) and 1 pump
Up to 3 sequences acting on the same modulating control (e.g. priority cooling/
dehumidification)
Room-supply air temperature cascade control with minimum/maximum limitation
of supply air temperature setpoint
General limitation function (minimum/maximum) with PI control action of
sequence controller, either as absolute limitation (e.g. for supply air temperature
or humidity), or as relative temperature limitation (e.g. maximum limitation of
room-supply air temperature differential)
Autonomous sequence controllers with P-, PI or PID control action
Disabling of individual sequences depending on the outside temperature
Demand-based ventilation, night purge
Sustained heating and cooling modes
Can also be used as differential controllers
Fans
Control and monitoring of a supply and extract air fan with preselected
command, preselected command feedback and hours run meter.
1-speed fan (recirculated air operation possible)
2-speed fan (locking the second speed depending on the outside
temperature)
Speed-controlled fan, including pressure or volumetric flow control
Release of fan overrun time for electric heating
Pumps
Control and monitoring of up to 4 single or twin pumps.
– Pump kick
Permanent on command at low outside temperatures
On according to load sequence controller or operating mode
Plant stop in the event of pump fault depending on the outside temperature
Heat recovery
Maximum economy changeover of a heat recovery system
Monitoring of efficiency of heat recovery system (with service messages)
Release relay heat recovery system
Anti-icing protection for the heat recovery system
Mixed air dampers
Maximum economy changeover of mixed air dampers
Minimum position of mixed air dampers
Startup and maximum position depending on the outside temperature
Mixed air temperature control at a constant setpoint
Linear step switch
Control of up to 3 aggregates by linear step switch
Binary step switch
Control of up to 3 aggregates by binary step switch
Variable step switch
Control of 2 aggregates by variable step switch with 6 or 4 steps
Logic functions
4 freely configurable logic function blocks to logically connect input variables
Frost protection
2-stage frost protection (modulating/2-position) or frost protection thermostat
(heating sequences delivering 100% output, hot water heating coil pump on,
fans off)
Demand-based ventilation (CO2/VOC), acting on the air dampers or the variable
speed/multispeed fans
Closed loop
control functions (cont’d)