Assortment / System Description

44
Boiler sequence controller RMK770
The RMK770 boiler sequence controller (see Data Sheet N3132) controls 1 to 6
heating boilers plus the boiler temperature, and can be used as a heating circuit
and/or primary controller.
T
P
V
V
P T
T
T
T
T
V
3132S40
T
Boiler sequence controller with integrated control and monitoring functions
18 programmed applications (tested plant types)
Free configuration of customized applications (basis: basic type K)
Extension modules for complementing the controller functions
KNX bus communication for operation and process information
Menu-driven commissioning, operation and monitoring (cleartext display)
No commissioning tool required for basic plants (easy configuration)
Commissioning of complex plants with the OCI700.1 service tool
Functions and characteristics
Relay outputs with... Product
no.
Digital
inputs
Universal
inputs
Analog
outputs
Ch'over contact No contact
RMK770
2 =
N.D1, N.D2
8 =
N.X1...N.X8
2 =
N.Y1, N.Y2
2 =
N.Q1, N.Q4
5 =
N.Q2, N.Q3, N.Q5,
N.Q6, N.Q7
The digital inputs N.D_ are ready configured for potential free status contacts.
The universal inputs N.X_ can be configured for use with passive sensors, active
signal sources, and status and pulse signals (see page 28).
Note: The universal inputs N.X_ of the RMK770 boiler sequence controller cannot be configured for
use with NTC 575 sensors.
The analog outputs NY_ and relay outputs N.Q_ are ready configured.
Brief description
Inputs and outputs
Inputs
Outputs