Assortment / System Description

53
Monitoring and recording mandatory events and functions (e.g. "Legionella"
function).
Monitoring of maximum value:
If data point "Limit value on" > "Limit value off", the maximum value is monitored
and displayed by the event logger under "Maximum".
Logic relationships of universal inputs
The measured value at input 1, OR Logic A, gives the switch on command for
storage tank charging.
The measured value at input 1, NAND Logic B, ends charging.
Operating line Setting value
[Logic A] function OR
[Logic B] function NAND
[Logic C] function AND
[Logic A switching value 1] on 30 °C
[Logic A switching value 1] off 35 °C
[Logic B switching value 1] on 65 °C
[Logic B switching value 1] off 60 °C
Logging measuring variables
24-hour log showing primary trend (solid line) and
reference trend of an additional channel (dotted line)
Examples
Event logger
Logic function block
Trend function