Assortment / System Description

56
Operating mode changeover from heating to cooling, or vice versa, takes place via
function block "H/C changeover".
The following types of changeover are available:
Via the operating mode selector (manually)
Via analog input (e.g. according to the outside temperature)
Via digital input (e.g. with a changeover thermostat installed in the flow)
According to a calendar date
If several types of changeover are activated, the following priorities apply:
Operating mode selector before
changeover input before
calendar.
2-pipe system "Heating/cooling" with production of heat and cooling energy.
Heating/cooling changeover is effected manually via the operating mode selector.
1 Production of heat
2 Production of cooling energy
3 Changeover valve
4 Manual heating/cooling changeover to changeover valve and function block "H/C changeover"
5 Forwarding of "Heating/cooling" changeover signal via the KNX bus
The RMB795B central control unit does not provide any closed loop control
functions (precontrol). Its main task is to collect the request signals and to forward
them to the heat or cooling energy source.
FB "H/C changeover"
23
Plant example