Assortment / System Description

57
Extension modules RMZ78x
The RMZ78x extension modules (see Data Sheets N3136 and N3146) are used to
extend the scope of functions of the Synco 700 controls RM.. and to increase the
number of inputs and outputs.
Extension modules can only be attached to Synco 700 controls RM.. (cannot
operate autonomously)
Extension modules are ready to operate as soon as they are connected to one
of the controls
The modules are powered via the controls
The modules are identified and monitored by the controls
The exchange of data between extension modules and controls is executed by
the controls. This means that the signals from the sensors, signal sources, etc.
are fed to the control where they are handled. The output signals and switching
commands generated by the control are forwarded to the respective extension
module
Use of the extension modules (types and numbers) depends on the type of
Synco 700 control
Types and numbers
Controls RM..
Type of extension module
RMU7x0B RMH760B RMK770 RMB795B RMS705B
Universal module RMZ785 --
Universal module RMZ787
Universal module RMZ788 -- --
Universal module RMZ789 -- -- --
Heating circuit module RMZ782B -- -- -- --
DHW module RMZ783B -- -- -- --
Number of modules per RM.. 4 4 3 3 4
The universal modules RMZ785, …787, …788, and …789 are suited for use with
all types of Synco 700 controls RM.., but consideration must be given to the type
of module and their number.
Relay outputs with…
Description and product no.
Universal
inputs
Analog
outputs
Ch’over contact NO contact
Universal module RMZ785 8 -- -- --
Universal module RMZ787 4 -- 1 3
Universal module RMZ788 4 2 1 1
Universal module RMZ789 6 2 2 2
Brief description
Overview
Universal modules