Assortment / System Description

58
The universal inputs N.X_ can be configured for use with passive sensors, active
signal sources, and status and pulse signals (see page 28). The analog outputs
N.Y_ and relay outputs N.Q_ are ready configured.
The extension modules RMZ782B and RMZ783B can only be used in connection
with the RMH760B heating controller.
Weather-compensated flow temperature control of heating circuit
via heating circuit mixing valve, 3-position or DC 0...10 V
Pump control (system or heating circuit pump)
Control of DHW heating and storage tank temperature
Storage tank charging via the common flow, with charging pump or mixing valve
Storage tank charging via external heat exchanger, with charging pump or
mixing valve
Relay outputs with…
Type of extension module
Universal
inputs
Analog
outputs
Ch’over contact NO contact
Heating circuit module RMZ782B 3 1 2 1
DHW module RMZ783B 4 1 3 2
The universal inputs N.X_ can be configured for use with passive sensors, active
signal sources, status and pulse signals, and sensors using NTC 575 sensing
elements.
Relay outputs with… Number of
modules
Type of extension
module
Universal
inputs
Analog
outputs
Ch’over contact NO contact
2 Universal module RMZ785 8 -- -- --
2 Universal module RMZ787 4 -- 1 3
2 Universal module RMZ788 4 2 1 3
Maximum number of modules: 4 per RMS705B
When using 1 RMZ785, 2 RMZ787 and 1 RMZ788 (maximum 4 modules per
RMS705B), the number of inputs and outputs can be increased, adding …
20 universal inputs,
2 analog outputs,
10 relay outputs: 3 with changeover contact, 7 with NO contact.
The order the different module types are fitted can be freely selected. But the
positions starting from the RM.. control unit must be set.
Position 1 Position 2 Position 3 Position 4
Inputs and outputs
Modules for RMH760B
heating controller
Heating circuit module
RMZ782B
DHW module RMZ783B
Inputs
Number of
inputs and outputs
Example RMS705B