Assortment / System Description

67
Application XCLC02 B24 HQ in HIT: With RXB24.1 room controller and application
CC-02.
After activating the required application, the room controller must be
parameterized, meaning that the following settings must be made:
Physical address (network address)
Zones (e.g. time switch zones, heat/refrigeration distribution zones LTE
mode)
Other parameters (e.g. Comfort heating setpoint, maximum supply air
temperature)
The QAX34.3 room unit as a "HandyTool" allows the RXB/RXL room controllers
to be parameterized via PPS2.
10385Z70
+ = counting/shifting "upward"
+ = counting/shifting "downward"
> = escape (quitting unconfirmed)
< = enter (confirmation)
Note: Room unit QAX34.3 is not suited for direct connection to the
KNX bus.
Parameter number Parameter name Basic setting Setting range
*034 Comfort heating setpoint 21 °C 10...40 °C
*108 Unit of temperature °C °C or °F
The room controllers can also be commissioned with the OCI700.1 service tool or
the ACS790.
In HIT
Commissioning