68
Room controllers RXB/RXL and central control unit RMB795B
Controls providing room functions should be located on the same KNX line as the
devices with which they exchange data via the KNX bus, which means:
RXB/RXL room controllers and RMB795B control unit on the same KNX line
In every room controller, the heat and refrigeration distribution zone is to be
configured with a zone address. Data exchange always takes place within the line.
On a line with RXB/RXL room controllers, the RMB795B central control unit is used
as a "collector".
In the "collector", the heat and refrigeration distribution zone on the generation side
is configured with a zone address. Data exchange in LTE mode takes place via line
couplers (Lc) and area couplers (Ac).
The "collector" forwards the room controllers’ heat/cooling energy demand to the
Synco 700 controllers for the production of heat and cooling energy.
1) Area/line coupler with LTE filter table: Normal (route)
2) Line coupler with LTE filter table: Route all
3) Area coupler with LTE filter table: Block all
Controls with room
functions
Central control unit
RMB795B as "collector"
Example