Assortment / System Description

70
Functions and characteristics
Room temperature control with the built-in sensor or an external room/return
temperature sensor
Heating/cooling changeover (automatically via local sensor or bus, or manually
via switch)
Selection of application via DIP switches or commissioning tool (when
commissioning with the ACS790 or ETS, all DIP switches must be set to OFF)
Selection of operating mode via operating mode button on the room thermostat
Temporary extension of Comfort mode
Display of current room temperature or setpoint in °C and/or °F
Minimum or maximum limitation of room temperature setpoint
Reset to factory settings (commissioning and control parameters)
Communication with Synco and other KNX-compatible controls via KNX
Display of outside temperature or time of day via KNX
Scheduling and central setpoint compensation via KNX
Synco controls use air demand signal from the room thermostats to optimize the
supply air temperature
1- or 3-speed fan control (automatically or manually)
2 multifunctional inputs, freely selectable for:
Operating mode changeover contact (Keycard) and H/C changeover sensor
External room or return air temperature sensor, dewpoint sensor
Electric heater enable
Monitoring input for temperature sensor or switch state
Extended fan functions: E.g. fan kick, fan start, selection of fan’s operating mode
(enabled, disabled, or depending on heating or cooling mode)
"Purge" function together with 2-port valve in a 2-pipe changeover system
Request to clean filters
Temperature limitation of floor heating system
4 buttons to control KNX actuators in KNX S-mode (switching groups with the
functions switching, dimming, blinds, and scenes)
Application Control outputs DIP switches
Factory setting Configuration via tool
- ACS790
- ETS
1
ON
23
- 1-stage compressor On/Off
- Chilled/heated ceiling On/Off
1
ON
23
2-pipe
heating or cooling
- 2-pipe fan coil unit 3-pos.
- Chilled/heated ceiling 3-pos.
3076D20
(B1)
M1
Y1
T
B2
T
T
(B1)
1
ON
23
2-pipe
with electric heater
heating or cooling
- 2-pipe fan coil unit On/Off
- Chilled/heated ceiling On/Off
- 1-stage compressor On/Off
Y1
M1
3171D21
T
B2
YE
T
(B1)
T
(B1)
1
ON
23
4-pipe
heating and cooling
- 4-pipe fan coil unit On/Off
- Chilled ceiling and radiator On/Off
- 1-stage compressor On/Off
T
Y2
Y1
M1
3076D22
(B1)
T
(B1)
1
ON
23
Common functions
of RD..
Specific functions
of RDF..
RDF301.50 only
Applications RDF..