Assortment / System Description

73
2 multifunctional inputs, freely selectable for:
Operating mode changeover contact (Keycard, window contact, etc.)
Changeover sensor for automatic heating/cooling changeover
External room or return air temperature sensor, dewpoint sensor
Electric heater enable
Monitoring input for temperature sensor or switch state
1 input DC 0...10 V for feedback of damper position
Temperature limitation of floor heating system
VAV systems
Application DIP switches
Factory setting, configuration via tool
- ACS790
- ETS
1
ON
23
OFF
45
1-duct
- Damper actuator DC 0…10 V
- Damper actuator 3-pos.
1 2 3 4 5
ON
OFF
1-duct with electric heater
- Damper actuator DC 0…10 V and electric heater on/off, PWM or 3-pos.
- Damper actuator 3-pos. and electric heater DC 0…10 V
1 2 3 4 5
ON
OFF
1-duct and radiator/floor heating system
- Damper actuator DC 0…10 V, radiator on/off, PWM or 3-pos.
- Damper actuator 3-pos. and radiator DC 0…10 V
1 2 3 4 5
ON
OFF
1-duct, air heating/cooling coil
- Damper actuator DC 0…10 V, heating/cooling coil on/off, PWM or 3-pos.
- Damper actuator 3-pos. and heating/cooling coil DC 0…10 V
1 2 3 4 5
ON
OFF
Application TBZB01 DG4 HQ in HIT: With RDG400KN room thermostat.
Specific functions
of RDG400KN
Applications
RDG400KN
In HIT