Assortment / System Description

95
Synco and KNX
KNX www.knx.org
is based on the European Installation Bus (EIB). EIB, BatiBUS
and EHS, the producers of bus technology, jointly developed the KNX standard for
HVAC plants, lighting and security technology, the objectives being the following:
Interworking of products of different manufacturers in the same network
Certification of products used in KNX communication networks
Backward compatibility with EIB (communication of KNX devices in S-mode)
In its simplest form, the KNX bus (see Data Sheet N3127) consists of a twisted pair
of wires, CE+ (red) and CE– (black), and a jacket.
3127Z05
CE
+
CE
In plants operating with Synco devices, bus cables without shielding are permitted.
If interference on the KNX bus is to be expected, the bus cable must be shielded.
The following types of Synco devices have a KNX bus connection facility, enabling
them to be integrated into a KNX network:
Universal controllers RMU710B, RMU720B, and RMU730B
Heating controller RMH760B
Boiler sequence controller RMK770
Central control unit RMB795B
Switching and monitoring device RMS705B
Room unit QAW740 and bus operator unit RMZ792 of the B-series
Room controllers RXB21.1, RXB22.1, RXL21.1, RXL22.1,
RXB24.1, RXL24.1, RXB39.1, and RXL39.1
Room thermostats RDF301, RDF301.50, RDU341, RDG100KN, RDG400KN
Central communication units OZW771.04, OZW771.10, and OZW771.64
Web servers OZW772.01, OZW772.04, OZW772.16, and OZW772.250
Service interface OCI700
Central apartment units QAX9.. (Synco living)
The Synco devices bear the following markings:
Devices carrying this logo are certified by KNX
TP1
Twisted Pair 1, 1 twisted pair of wires (transmission medium)
EE
Easy (mode), Logical Tag Extended (configuration mode)
The Synco devices communicate with each other via zone addresses in LTE
(Logical Tag Extended) mode.
Synco devices and KNX devices supplied by thirds communicate with each other
via group addresses in S-mode (S = System Mode). For S-mode addressing,
commissioning tool ETS Professional is required.
The Synco devices can simultaneously communicate in LTE mode and S-mode.
KNX bus
Shielding of bus cable
Synco and KNX
Product markings
LTE mode, S-mode