Assortment / System Description

98
KNX network coupled with IP network via IP router (area line 0)
LTE filter table: 1) Normal (route), 2) Route all
Alarm drains – in the above example, the OZW772 web server and the RMZ792
bus operator unit – must receive all alarm signals and all other data from the
network and, for this reason, must be installed on a superposed line.
Main line 2 acts as a "backbone" and the alarm drains need be installed on that
line. Area coupler Ac 2.0.0 must be set to "Route all telegrams".
Note: A maximum of 64 bus devices can be installed on one line. Addresses x.y.250 (see example)
shall refer to the highest possible address for bus devices and not to the possible number of
bus devices.
Example
Alarm drains