Assortment / System Description

99
Engineering tool software, ETS Professional
Communication between Synco devices takes place in LTE mode via LTE data
points.
Communication between Synco devices and third-party KNX devices is executed
in S-mode via S-mode data points. In the Synco devices, the S-mode data points
correspond to a subset of the LTE data points.
The S-mode data points of the current Synco devices are available for downloading
from Siemens Building Technologies as an import file for ETS Professional.
The S-mode data points are to be configured in ETS Professional. The tool can be
ordered with the KNX Association: http://www.knx.org/
The top section of the screen shows that for the Synco living central apartment unit
QAX913, the parameters for "Switching groups [1...8]" are selected and set for
"Switching group 1: Function" "Blind".
Resulting from parameter setting "Switching group 1: Function" "Blind", the
bottom section of the screen shows the following S-mode data points (in ETS
"Device objects"):
36 [Switching group 1] Blind Up/Down Object function: Transmit
37 [Switching group 1] Blind Step/Stop Object function: Transmit
39 [Switching group 1] Trigger Up/Down Object function: Receive
Note: The data point numbers 1...8 comprise the general S-mode data points, contained
in every KNX Synco device.
LTE mode data points
S-mode data points
Engineering Tool
Software, ETS
Example:
Tool interface ETS4