10.2.3 Load-dependent by controller
The pump can be switched on load-dependent by the controller (see section 15.1.1
"Assign aggregates to sequences").
The co
ntrollers can be used for up to three wiring connections; maximum selection
applies. The switch-on and switch-off points can be entered via the settings "Load-
dependent ON" and "Load-dependent OFF". In normal use, we recommend
switching on the pump at 5% load and switching it off at 0% load.
M
N Y1
DO
N Q1
A
y1 y2 y3
A
Mod output
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Pump 1...4
Operating line Range Factory setting
Load-dependent ON 0...100% 5%
Load-dependent OFF 0...100% 0%
If the value "Load-dependent ON" is smaller than "Load-dependent OFF", the
control action is reversed.