Basic Documentation

120/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Aggregates 03.10.2011
In a wiring test, the pumps can be switched on or off directly via the control switch.
Main menu > Commissioning > Wiring test > Outputs>
Operating line Comments
Pump 1A / Pump 1B Off, On
Pump 2A / Pump 2B Off, On
Pump 3A / Pump 3B Off, On
Pump 4A / Pump 4B Off, On
10.2.16 Priorities
The following priorities apply to pump operations:
1. On / Off during wiring test
2. Off by pump supervision (flow signal, overload signal)
3. OFF via locking time with run priority changeover (for twin pumps)
4. On by frost protection (load-dependent ON after heating sequence
5. OFF via messages with plant stop (only for pumps switched on directly via
operating mode)
6. ON via switch-off delay
7. OFF via stop conditions (1+2)
8. ON via start conditions (1+2)
9. ON by outside temperature
10. On by pump kick
11. Load-dependent ON
12. Preselection in normal operation for pumps switched on directly by the
operation mode (see section 10.2.2 "Operating mode")
10.2.17 Assign texts
The texts for the motors can be adapted via operation. They are displayed at the
relevant operating line and on the menu.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Pump 1...4 >
Operating line Range Factory setting
Pump x Max. 20 characters Pump x
All pump faults possess adjustable alarm texts:
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Pump 1…4 >
Operating line Range Factory setting
[Pump 1] fault
Max. 20 characters
[Pump 1] fault
[Pump 1] overload
Max. 20 characters
[Pump 1] overload
[Pump 1] no flow
Max. 20 characters
[Pump 1] no flow
[Pump 1A] overload
Max. 20 characters
[Pump 1A] overload
[Pump 1B] overload
Max. 20 characters
[Pump 1B] overload
[Pump 1A] no flow
Max. 20 characters
[Pump 1A] no flow
[Pump 1B] no flow
Max. 20 characters
[Pump 1B] no flow
[Pump 1] precom no
checkb sign
Max. 20 characters
[Pump 1] precom
no checkb sign
Wiring test
Setting values