Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Aggregates 03.10.2011
10.2.18 Operating hours
The total number of operating hours is acquired for each pump output. The counter
counts to max. 99 999 hours and then rolls over to 0.
Main menu > Aggregates > Pump 1…4 >
Operating line Range
Operating hours pump A
Optg hours pump A
0...99,999 h
Operating hours pump B
Optg hours pump B
0...99,999 h
The counter reading can be adapted and e.g. reset to 0 at the password level.
Main menu > Settings > Aggregates > Pump 1...4 >
Operating line Range Factory setting
Optg hours pump A 0...99,999 h 0
Optg hours pump B 0...99,999 h 0
10.3 Modulating output
This function provides a continuous DC 0...10 V output signal for a modulating
actuator requiring an appropriate input signal.
B
C
730
720
D
730
A
y1 y2 y3
y1 y2
y3
y1 y2
y3
y1 y2 y3
A
B
CD
The modulating output is not suitable for controlling an electric heating coil with a
current valve.
The Step switch function is best suited for applications with a relay configured as
switch-on agent for the electric heating coil, a modulating output signal DC 0…10 V
and an input as flow monitor for release.
10.3.1 Activate block
To activate the "Modulating output" function, an output must first be assigned.
Main menu > Commissioning > Extra configuration > Aggregates > Modulating outputs >
Modulating output A...D >
Operating line Adjustable values / remarks
Modulating output A,
…Modulating output D
---, N.Y1, N.Y2, ... / activate modulating output
For each type of universal controller, the following number of "Modulating output"
blocks is available:
RMU710B: max. 2 blocks
RMU720B: max. 3 blocks
RMU730B: max. 4 blocks
Display values
Setting values
Note
Configuration