Basic Documentation

123/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Aggregates 03.10.2011
10.3.4 Start condition
The modulating output can be activated via a digital signal.
The output signal is delivered while giving consideration to the limitation.
If the start signal is withdrawn, the output delivers 0 V or, in case of inversion,
10 V.
A maximum selection is generated.
If no start condition is configured, the output is always active.
Main menu > Commissioning > Extra configuration > Aggregates > Modulating outputs >
Modulating output A...D >
Operating line Adjustable values / remarks
Start condition ---, N.X1, N.X2, ... (digital only).
10.3.5 Assign texts
Text can be assigned to each modulating output.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Modulating output A…D >
Operating line Range Factory setting
Modulating output A… Max. 20 characters Modulating output x
10.3.6 Function check / wiring test
The current state of modulating output x is displayed on the operator unit.
Main menu > Aggregates >
Operating line Comments
Modulating output A… 0...100%
During the wiring test, the modulating output can be directly controlled via the
control switch.
Main menu > Commissioning > Wiring test > Outputs >
Operating line Comments
Modulating output A… ----, 0...100%
Setting values
Display values
Wiring test