Basic Documentation

130/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Aggregates 03.10.2011
Heating and dehumidifying
Eh
Su
Ex
Oa
3150D15
Without cooling valve setting With cooling valve setting
C
c
l
H
c
l
Hcl
Su
Ex
Ccl
Oa
3150D16
C
c
l
H
c
l
Hcl
Su
Ex
Ccl
Oa
3150D17
Ex Extract air Hcl Heating coil
Oa Outside air Ccl Cooling coil
Eh Exhaust air
Su Supply air
The HR output can be inverted.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Heat recovery equipment >
Operating line Range Factory setting
Inversion No, Yes No
Meaning:
No: 0...100% Load = 0...100% output
Yes: 0...100% Load = 100...0% output
10.4.6 Motor kick
A periodic motor kick can be activated to avoid soiling (dust) and seizing of HR
during extended off periods.
When motor kick is active, HR is switched on for 30 seconds once a week
regardless of any other functions and settings.
The motor kick is activated by setting "Motor kick" to "Yes". If the setting is "No",
there is no motor kick.
In addition, a kick day and time can be set.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Heat recovery equipment >
Operating line Range Factory setting
Motor kick Yes, No No
Kick day Mo, Tu, We, Th, Fr, Sa, Su Mo
Kick time 00:00...23:59 h.m 10:00 h.m
Example
Setting values
Setting values