Building Technologies Summary 03.10.2011
1.6 Application concept
1.6.1 Programmed application
Each universal controller contains 5 tested, preprogrammed applications.
The simplest commissioning method is to activate one of the programmed
applications.
The 5 internally loaded application per controller are described:
In this basic documentation in section 31.2 "Configuration diagrams"
In data sheet N3150
In the installation instructions G3151
On the operator unit display, the operating line "plant type" displays:
A01 (AEFB01 U3B HQ)
Meaning:
A
The standard application corresponds to basic type A
01
First internally loaded standard application
AEFB01 U3B HQ
The name in parentheses is the application’s code. It
corresponds to the designation of the application sheet
If the plant type line only displays a letter, it means that basic type A, P, C or U is
loaded. Without making adaptations on the extra configuration line, such an
application does not work.
Depending on the controller type, supplemental country-specific application are
loaded on the universal controller.
1.6.2 Adapted application
The programmed application is not entirely correct, but an adapted application is
included in HIT (www.siemens.com/HIT
). In that case, enter appropriate settings in
the "Extra configuration" menu.
1.6.3 Free configuration
The application you want is not described; you have to set up the configuration
from scratch. Configuration diagrams allow the plant controlled to be adapted (refer
to section 31.2 "Configuration diagrams".
Y
ou can save time by starting with a similar internally loaded or similar application
sheet and edit only the differences.
Example
Note
Recommendation