10.6.2 Linear step switch
The linear step switch connects the relay outputs in equal steps.
Load connection applies the following pattern:
Q
0 %
Y+Q
Y
Q
0 %
Y+Q
X
P
X
P
100 %
100 %
Y
Step 1
Step
2
Step
3
Step
4
Step
4
Step
3
Step
1
Step
2
3150D12en
Switching distance, example with 2 digital outputs:
0% 100%
x x x x x x
0% 100%
Y1
Q2
Q1
ΒΌ x
3150D26
Q
0Y + 2Q
ON
ON
OFF
OFF
1Y + 2Q
Q
MAXPOS
MINPOS
Distance X is equal to 100% load divided by (number of steps +1).
To prevent excessively quick runup, you can enter a common startup delay time.
This delay makes the controller wait for the set time between the steps during
startup.
With the linear step switch, you can set a priority changeover of the outputs. The
priorities change at fixed intervals every week (always after 7 x 24 = 168 hours).
Changeover is as follows (example with 4 steps):
Week 1: 1, 2, 3, 4
Week 2: 2, 3, 4, 1
Week 3: 3, 4, 1, 2
Week 4: 4, 1, 2, 3
Week 5: 1, 2, 3, 4
Priority changeover is reset by a power outage.
Load connection
Note on diagram
Startup delay
Run priority changeover