Basic Documentation

143/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Aggregates 03.10.2011
10.6.4 Cascade step switches
To increase the number of steps, two or three linear/binary step switches can be
interconnected (cascaded).
Main menu > Commissioning > Extra configuration> Aggregates > Step switch > Step
switch 1…2 >
Operating line Range Factory setting
Connect 1+2 No, Yes No
Connect 2+3 No, Yes No
If two linear/binary step switches are interconnected (cascaded), the outputs of
the sequence controller must be connected only to the first step switch
The modulating output of the 2nd (with 2) or 3rd (with 3) step switches must be
configured as modulating load signal
The type of both step switches should be equal: binary or linear
Cascading is without effect, if the 2nd step switch is inactive
There may not be gaps in configuration; thus, steps 1, 2 and 3 rather than steps
1, 3 and 4
If two or three step switches are cascaded, the settings for locking time, overrun
time, startup delay (linear only) as well as external release must be set for all
step switches; the settings are not passed on
Startup delay (linear only) and run priority changeover act only within the
respective step switch
Binary step switch cascaded at 256 load increments:
N.X1
Y
SIGNAL Y
x
A7.Q1
Q
A7.Q2
Q
Q
N.Q2
Q
N.Y1
Y
N.Q3
Q
N.Q1
N.Q6 N.Q7
QQ
Q
N.Q4
123
4
y1 y2
x
QQ Q
QY
y3
123
4
y1 y2
x
QQ Q
QY
y3
730
720
730
730
730
S1 S2 S3 S4S5 S6 S7 S8 Y
S3 S2 S1 S4 S5
yp yp yp yp yp
a
d
Step
switch 1
Linear
Binary
Release
Connect 1+2
Step
switch 2
Linear
Binary
Release
Connect 2+3
SAT
Controller 1
(Ventilation)
With supply air limitation
Cascade
Constant (supply air)
Cascade/const (alternating)
Seq. limit. Casc/Const
3150s50en
The greater load increments (S5 to S8) of the first step switch are subdivided by
the smaller increments (S1 to S4) of the second step switch.
Step switch 1: Greater load increments.
4 Q S5 = 16/256 S6= 32/256 S7 = 64/256 S8 = 128/256
Step switch 2: Smaller load increments.
1Y+4 Q Y = 0.. 1/256 S1 = 1/256 S2 = 2/256 S3 = 4/256 S4 = 8/256
Configuration
Notes on configuration
Example 1
Load connection