10.7.5 Release external
One input can be configured as release for the step switch.
Main menu > Commissioning > Extra configuration> Aggregates > Step switch > Step
switch 4...5 >
Operating line Adjustable values / remarks
Release external ---, N.X1, N.X2, ... (digital and analog inputs)
An analog signal can be used as release signal.
The threshold values can be set via the setting values "Release switching value
on" and "Release switching value off", if the corresponding step switch is to be
released.
Main menu > Commissioning > Settings > … or
Main menu > Settings > Aggregates > Step switch > Step switch 4…5 >
Operating line Range Factory setting
Release switching value on Depending on selected type Depending on type
Release switching value off Depending on selected type Depending on type
A delay time can be set to account for measurement variations during operation.
For example, the following function can be implemented: Release of an electric
heating coil via a flow signal.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Step switch > Step switch 4…5 >
Operating line Range Factory setting
Switch-off delay release 00.00...10.00 m:s 00.05 m:s