Basic Documentation

155/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Aggregates 03.10.2011
The changeover impacts all time-related parameters of the logic function block
(switch-on/off delay and min. switch-on/off time).
The time format “h:m“ can be set in 10-minute increments.
10.8.2 Assign texts
A specific text can be assigned to each logic and operation selector. This text
appears on the menu and in the operating line.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions > Logic 1...4 >
Operating line Range Factory setting
Logic 1...4 Max. 20 characters Logic 1...4
Operation selector 1...4 Max. 20 characters Operation selector 1...4
Refer to section 31.4 for an overview of all editable texts and on how to reset them.
10.8.3 Setting values switching value On and Off
The logic can process digital and analog signals. Setting values "[Logic x switching
value n] on" and "[Logic x switching value n] off" are used to convert a continuous
signal to a 2-position "on / off" signal.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions > Logic 1...4 >
Operating line Range Factory setting
[Logic A switching value 1] on Depending on select. type Depending on type
[Logic A switching value 1] off Depending on select. type
Depending on type
[Logic A switching value 2] on Depending on select. type
Depending on type
[Logic A switching value 2] off Depending on select. type
Depending on type
[Logic A switching value 3] on Depending on select. type
Depending on type
[Logic A switching value 3] off Depending on select. type
Depending on type
[Logic B switching value 1] on Depending on select. type
Depending on type
[Logic B switching value 1] off Depending on select. type
Depending on type
[Logic B switching value 2] on Depending on select. type
Depending on type
[Logic B switching value 2] off Depending on select. type
Depending on type
10.8.4 Switch-on delay / switch-off delay
For the logic output, a switch-on delay and switch-off delay can be set.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Aggregates > Logic functions > Logic 1...4 >
Operating line Range Factory setting
Switch-on delay 00.00...59.59 m:s 00.00 m:s
Switch-off delay 00.00...59.59 m:s 00.00 m:s
The switch-on delay always acts on the switch-on command, the switch-off delay
on the switch-off command.
Important
Setting values
Setting values
Setting values