Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Temperature controller (basic type A) 03.10.2011
When exiting the Commissioning menu, a check is made to see if the room
temperature, extract air temperature or supply air temperature are connected. If the
corresponding temperature is connected but missing later, a message appears.
No. Text Effect
101…
[N.X1] sensor error Non-urgent message; must not be
acknowledged
60 Room sensor error plant 1 Non-urgent message; must not be
acknowledged
If the main controlled variable is missing, the plant is switched off and fault
message "[Main contr var 1] sensor error" is triggered.
No. Text Effect
3011 [Main contr var 1] sensor error Urgent message, with plant stop;
must not be acknowledged.
Control mode Main controlled variable
Supply air temperature control Supply air temperature
Room temperature control Room temperature
Extract air temperature control Extract air temperature
Room temperature control with supply air
limitation
Room temperature
Extract air temperature control with supply air
limitation
Extract air temperature
Room/supply air temperature cascade control Supply air temperature
Extract air/supply air temperature cascade control Supply air temperature
If the input identifier for room temperature is configured in addition to the correctly
set control mode next to the input identifier extract air temperature, control always
occurs with extract air temperature.
The room temperature can be used for functions such as sustained mode, night
cooling to send to the bus or for display.
The effect of having one or several input identifiers connected at the same time is
described in detail in section 8.3 Special analog inputs.