Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Temperature controller (basic type A) 03.10.2011
Main menu > Controller 1 >
Operating line Comments
Actual value room temp
Current room temp setpoint
Operating line Comments
Actual value extract air temp
Current setp extract air temp
11.5.3 Supply air limiter
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Controller 1 > Supply air limiter >
Operating line Range Factory setting
Limit value high 35.0 °C
Limit value low
16.0 °C
Differential high 0.0...500.0 K 50.0 K
Differential low 0.0...500.0 K 50.0 K
Reduction min limitation cooling 0...50 K 0.0 K
P-band Xp 0.0…500.0 K 15 K
Integral action time Tn 00.00...59.55 m:s 02.00 m:s
11.5.4 Operating principle
It is possible to enter absolute and relative limitation. If only one of the these
functions is desired, the other function can be deactivated by setting the setpoints
far outside.
If there is no supply air temperature sensor, limitation is set inactive.
Supply air limitation, absolute
If the Limit value high or Limit value low is exceeded, the limiter function overrides
the normal control function with PI control to adhere to the limitation setpoint.
x
w
T
T
[Limit value high]
[Limit value low]
- [Set back]
Limitation max
Limitation min
3140S02en
A
cts an all sequences
Setpoint shift
Display values for room
temperature control
Display values for extract
air temperature control
Setting values
Application example