Basic Documentation

170/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Temperature controller (basic type A) 03.10.2011
Source air opening: Laminar air flow in occupancy area. Supply air may be
introduced e.g. max 4 K below the room temperature.
1,5 m
w
w
x
x
T
T
x
w
[Limit value high]
[Limit value low]
Limitation max
Limitation min
3140S01en
Acts an all sequences
Setpoint shift
SpSu
t
RT
Supply air limit
value max
Supply air limit
value min
Max limitation
supply air delta
Min limitation
supply air delta
Supply air temp
limit value max
Supply air temp
limit value min
Actual value room temp
3140D04en
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Controller 1 > Cascade controller >
Operating line Range Factory setting
Supply air limit value max 35.0 °C
Supply air limit value min 16.0 °C
Max limitation supply air delta 0.0…50.0 K 50.0 K
Min limitation supply air delta 0.0…50.0 K 50.0 K
Room influence Xp 1.0…100.0 4 K
Room influence Tn 00.00...59.55 mm:ss 10.00 m:s
11.6.2 Room setpoints
Specific setpoints can be predefined for operating modes Comfort, Precomfort
and
Economy.
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Controller 1 > Room setpoints >
Main menu > Controller 1 >
Operating line Range Factory setting
Economy cooling setpoint 30 °C
Precomfort cooling setpoint 28 °C
Comfort cooling setpoint 24 °C
Comfort heating setpoint 21 °C
Precomfort heating setpoint 19 °C
Economy heating setpoint 15 °C
See Section 11.10
Applicatio
n example
Function diagram
Setting values
Setting values
Setpoint limitations