Basic Documentation

178/332
Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Supply air temperature controller, demand-controlled (type P) 03.10.2011
12 Supply air temperature controller,
demand-controlled (type P)
12.1 General
730
720
730
N.X1
Controller 1 is intended for demand-controlled supply temperature control with
individual VAV room controllers. Input N.X1 is reserved for the supply air
temperature sensor. Controller 2 and 3 are universal controllers.
The following controllers (sequence controllers) are available:
RMU710B: Controller 1
RMU720B: Controller 1, Controller 2
RMU730B: Controller 1, Controller 2, Controller 3
12.2 Activate function
Main controlled variable configuration occurs via basic type selection.
Main menu > Commissioning > Extra configuration > Controller 1 > Inputs >
Operating line Adjustable values / remarks
Main controlled
variable
N.X1 (read-only).
12.2.1 Further procedure to configure the controllers
Action Notes in…
The following auxiliary functions can be activated additionally:
Universal shift.
General limiter
Sequence limiter
Sequence locking acc to OT
Control timeout
Section 15.6
Section 15.2
Section 15.3
Section 15.4
Section 15.8
Assign to the individual sequence outputs. Section 15.1.1 …15.1.3
A deviation message can be activated for each controller. Section 15.7
Control parameters controller 1-3 Section 15.1.4
12.2.2 Limits and setpoint effects
The following function can have an impact on the supply air setpoints:
Universal shift (e.g. by outside temperature).
Configuration