Siemens Universal controllers RMU710B, RMU720B, RMU730B CE1P3150en
Building Technologies Flow temperature, demand-controlled (basic type C) 03.10.2011
13.5 Setpoints
A "Chilled water flow setpoint" and a "Flow temperature increase max" can be set.
With 2-pipe systems, it is also possible to set a "Heating flow setpoint" and a "Flow
temperature reduction max". Both functions are switched off by default (= 0 K).
w
CwFl
6 °C
3140D31en
FT boost max
Key:
w
CwFl
Chilled water flow setpoint
The "Chilled water flow setpoint" can be shifted via universal shift.
20 °C
w
CwFl
30 °C
12 °C

6 K
FT boost max
end start
Setp comp 2
3140D32en
Main menu > Commissioning > Settings > .... or
Main menu > Settings > Controller 1 > Setpoints >
Operating line Range Factory setting
Heating flow setpoint
1)
-50...250 °C 40 °C
Flow temperature reduction max
1)
0...100 K 0 K
Chilled water flow setpoint -50...250 °C 6 °C
Flow temperature increase max 0...100 K 0 K
1)
Available only for configuration of a 2-pipe system
Main menu > Controller 1 >
Operating line Comments
Actual value
Current setpoint
Function diagram
Function diagram
Setting values
Display values