2.2.4 Access rights
An access right is defined for each parameter (operating line). There are 3 access
levels:
Level Access Symbol
User level (for the
plant operator)
The user level is always accessible.
The user can adjust visible, editable operating
lines
Service level
(for maintenance)
Press the OK knob and the ESC button at the
same time, then select operating line "Service
level" and confirm by pressing the OK knob
Password level
(for
commissioning)
Press the OK knob and the ESC button at the
same time; then, select operating line "Password
level" and confirm by pressing the OK knob; then,
enter the number 7 for the password and confirm
by pressing the OK knob
The access level determines which individual menus and operating lines are
activated. At a higher access level, all of the menus and operating lines of the
lower access levels remain visible.
The levels use a common menu tree as a base (the password level shows the
entire menu tree).
After time-out (= 30 minutes, during which the controller is not operated), the
controller switches to the user level
Switching from the current access level to another access level:
1. Press the OK knob and the ESC button simultaneously. The "Access levels"
menu appears
2. Select the required access level by turning the OK knob and press to
confirm
3. Enter number 7 to access the password level
Switching to another
access level